-  - Accelerator Personnel do not have any control over the main Fire Alarm Systems, we only have the ability to view information. ​ Accelerator Personnel (Devon or Don) are, however, the primary technical support for the VESDA systems in the lab areas. +**Actions if the building ​fire alarm activates:**
-  - If the fire alarm activates:+
     - The designated Accelerator Operator shall:     - The designated Accelerator Operator shall:
-        * Check the annunciator panel for the location of the alarm (more on the panel below)+        * Check the annunciator panel for the location of the alarm (instructions ​on the panel below)
         * Put in all faraday cups and shut down the accelerator         * Put in all faraday cups and shut down the accelerator
 +        * Contact accelerator staff ASAP
         * Wait for emergency personnel in the lobby and escort them to the location         * Wait for emergency personnel in the lobby and escort them to the location
     - All other personnel are to evacuate the building as directed by the alarm system message     - All other personnel are to evacuate the building as directed by the alarm system message
-  ​- If the fire alarm is in a condition other than normal, no radiation will be produced until the trouble is fixed, or until the requirements in the Interlock Rules Policy have been satisfied. + 
-  ​Accelerator Personnel may use a fire extinguisher if the individual feels they can do so safely but there is no requirement to do so. +**Actions if the annunciator panel reports Supervisory:​** 
-  ​Never open a door to an alarm area if smoke is visible outside the door or if the door is warm. + 
-  ​OUPD dispatchers should get automatically notified of any trouble or fire alarm on the system.+The designated Accelerator Operator shall: 
 +    ​Immediately stop radiation production 
 +    - Check the annunciator for the nature of the trouble (instructions on the panel below) 
 +    - If the message is "DOCK or VAULT ECO SENSOR ALARM" this is a low oxygen event 
 +      - The VESDA computer should be playing a low oxygen message, check to see if the computer is reporting low oxygen. 
 +      - Check to see if the SF6 alarm and Tank Volume data support an SF6 leak 
 +      - Contact accelerator staff immediately 
 +      - Be prepared to go to the nearest fire alarm pull station to evacuate the building 
 +    - If the message is "​XXXXXXXX VESDA PIPE X" This is a significant smoke detection 
 +      - Contact accelerator staff immediately 
 +      - Activate the Tritium Exhaust Fans 
 +      - Be aware that the building fire alarm may activate soon 
 + 
 +**Actions if the annunciator panel reports Trouble:​** 
 + 
 +The designated Accelerator Operator shall: 
 +    - Immediately stop radiation production 
 +    - Check the annunciator for the nature of the trouble (instructions on the panel below) 
 +    - If the message is "​XXXXXXXX VESDA PIPE X" This is an initial smoke detection 
 +    - Contact accelerator staff immediately 
 +    - Be aware that the Supervisory Trouble and then the building fire alarm may activate soon 
 + 
 +__........................................................................................__ 
 + 
 +**General Information:​** 
 +  * Accelerator Personnel do not have any control over the main Fire Alarm Systems, we only have the ability to view information. ​ Accelerator Personnel (Devon or Don) are, however, the primary technical support for the VESDA systems in the lab areas. 
 +  * If the fire alarm is in a condition other than normal, no radiation will be produced until the trouble is fixed, or until the requirements in the Interlock Rules Policy have been satisfied. 
 +  ​Accelerator Personnel may use a fire extinguisher if the individual feels they can do so safely but there is no requirement to do so. 
 +  ​Never open a door to an alarm area if smoke is visible outside the door or if the door is warm. 
 +  ​OUPD dispatchers should get automatically notified of any trouble or fire alarm on the system.
  
 **The Annunciator Panel** (located in the control room, photo below) **The Annunciator Panel** (located in the control room, photo below)