The lower right pane will display a list of events for that detector. In addition to actual detections, and event may also be generated by system trouble. For example, “low air flow”, or “calibration due”.
Any events on the VESDA systems will automatically email Don and text/email Devon.
Any events on the smoke detection devices will appear on the main fire alarm system.
Any trouble events on the O2 detectors appear on the computer and the Fire Alarm System. Both low oxygen events appear on the computer and play messages on the computer speakers, and major low oxygen events appear on the Fire Alarm System as Supervisory.
Any smoke events that caused trouble or supervisory conditions on the fire panel may be cleared by Devon or Don after the smoke levels return to normal values below the green lines.
Any smoke events that cause a fire alarm may only be cleared after smoke levels return to normal or after Devon or Don disable that particular detector. Facilities management or the Fire Department will have to reset the main fire panel.