Actions if the building fire alarm activates:

  1. The designated Accelerator Operator shall:
    • Check the annunciator panel for the location of the alarm (instructions on the panel below)
    • Put in all faraday cups and shut down the accelerator
    • Contact accelerator staff ASAP
    • Wait for emergency personnel in the lobby and escort them to the location
  2. All other personnel are to evacuate the building as directed by the alarm system message

Actions if the annunciator panel reports Supervisory:

The designated Accelerator Operator shall:

  1. Immediately stop radiation production
  2. Check the annunciator for the nature of the trouble (instructions on the panel below)
  3. If the message is “DOCK or VAULT ECO SENSOR ALARM” this is a low oxygen event
    1. The VESDA computer should be playing a low oxygen message, check to see if the computer is reporting low oxygen.
    2. Check to see if the SF6 alarm and Tank Volume data support an SF6 leak
    3. Contact accelerator staff immediately
    4. Be prepared to go to the nearest fire alarm pull station to evacuate the building
  4. If the message is “XXXXXXXX VESDA PIPE X” This is a significant smoke detection
    1. Contact accelerator staff immediately
    2. Activate the Tritium Exhaust Fans
    3. Be aware that the building fire alarm may activate soon

Actions if the annunciator panel reports Trouble:

The designated Accelerator Operator shall:

  1. Immediately stop radiation production
  2. Check the annunciator for the nature of the trouble (instructions on the panel below)
  3. If the message is “XXXXXXXX VESDA PIPE X” This is an initial smoke detection
  4. Contact accelerator staff immediately
  5. Be aware that the Supervisory Trouble and then the building fire alarm may activate soon

…………………………………………………………………………….

General Information:

The Annunciator Panel (located in the control room, photo below)

The control room annunciator is the only point where accelerator personnel have access to system information. The main panel and the front door panels are behind locked doors.

There are 4 possible conditions for the fire alarm system:

The Priority 2 alarm is not used in our system and we should not ever see such alarms.

The gray buttons and LEDs on the left side of the annunciator do nothing for us. The LEDs may illuminated during maintenance to indicate that certain functions are disabled for repairs.