==== Switching Extension Legs ==== ** Switching Extension Legs ** - Run current to zero and turn power to quad(s) off if needed. - Turn power to leg selection panel on (white lights will come on) if not already on. - Push button to select leg. - Turn power off (interlock light for beam line will change to leg selected). - Turn power on again. - Turn quad supply on (switch on right that says "lens power/off"). - You can now operate quad(s) for selected line. - NOTE Quad 4 selection between the R-23 and R-45 beamlines is NOT done by leg selector panel; this is controlled by a switch in the large target room. NOTE: Always turn quad power off before attempting to switch legs. Switching magnet polarty must be done in a separate operation. * Original Credits * Maintained by: Thomas N. Massey Office: Accelerator Lab 217 Telephone: (740)593-0933 E-Mail: MASSEY@OHIOU.EDU Last modified on 10/29/98