playground:fire
This is an old revision of the document!
- Accelerator Personnel do not have any control over the Fire Alarm Systems, we only have the ability to view information.
- If the fire alarm activates:
- The designated Accelerator Operator shall:
- Check the annunciator panel for the location of the alarm (more on the panel below)
- Put in all faraday cups and shut down the accelerator
- Wait for emergency personnel in the lobby and escort them to the location
- All other personnel are to evacuate the building as directed by the alarm system message
- If the fire alarm is in a trouble condition no radiation will be produced until the trouble is fixed, or until the requirements in the Interlock Rules Policy have been satisfied.
- Accelerator Personnel may use a fire extinguisher if the individual feels they can do so safely but there is no requirement to do so.
- Never open a door to an alarm area if smoke is visible outside the door or if the door is warm.
The Annunciator Panel (located in the control room, photo below)
playground/fire.1339534316.txt.gz · Last modified: (external edit)

