| - | **Quadrupole Computer Controls** | + | ====== |
| + | * There are 4 quadrupole magnets [[http:// | ||
| - | {{playground: | + | * These magnets and their control power supplies have been upgraded to computer control from the original potentiometer control. |
| + | * Each quadrupole magnet has 2 power supplies designated QuadA and QuadB with independent current adjustments. | ||
| + | * A sample computer control window is shown below. | ||
| {{quad.jpg}} | {{quad.jpg}} | ||
| + | * Ideally, the A and B currents should be equal to focus a symetric beam entering the quadrupole on its center axis. | ||
| + | * The computer control window displays a graph window with QuadA current indicated on the X-Axis and the QuadB current indicated on the Y-Axis. | ||
| + | * The diagonal line is the locus of points A = B for reference. | ||
| + | * The QuadA and QuadB currents are adjusted by moving the bullseye cross hair graphic. | ||
| + | * The QuadA and QuadB currents are displayed in text under the X axis. The X and Y full scale values are fixed at 50 Amps. | ||
| + | * The **Grab** mode allows you to set the mouse pointer over the bullseye and while depressing the left mouse button, drag the bullseye to another set of A and B current values. | ||
| + | * After presetting the quad currents to an approximate value using the Grab mode, an initial beam tune of the quadrupole would often be to switch to the mode **A=B**. | ||
| + | * In the **A=B** mode, the A current is made equal to the B current and the currents are simultaneously adjusted by moving the mouse left and right with the left mouse button depressed. | ||
| + | * In the **dA=dB** mode, the dA current (change in A current) is made equal to the dB current and the currents are adjusted by moving the mouse left and right with the left mouse button depressed. | ||
| + | * When in the **A=B** mode or **dA=dB** mode, pressing the **Fine** button will result in a free form mode with the sensitivity set to Med. | ||
| + | * When in the **A=B** mode or **dA=dB**, pressing the **Coarse** button will result in a free form mode with the sensitivity set to Grab. | ||
| + | * When the mouse cursor is moved below the X axis and to the left of center **Step Mode QuadA** allows adjusting the QuadA currents up and down 1 step at a time using the same resolution that the mouse movements were using. | ||
| + | * When the mouse cursor is moved below the X axis and to the right of center **Step Mode QuadB** allows adjusting the QuadB currents up and down 1 step at a time using the same resolution that the mouse movements were using. | ||
| + | * Momentarily depressing the left mouse button when in the main field of the plot will set the step resolution 1 level finer. | ||
| + | * Momentarily depressing the right mouse button when in the main field of the plot will set the step resolution 1 level more coarse. | ||
| + | * The **Save** button will save the current values of the QuadA and QuadB currents. | ||
| + | * Sometimes, when a large step in quad current is attempted too quickly, the power supply currents will start oscillating and will not respond to adjustments of the computer control. | ||
| + | |||
| + | // | ||