playground:fire
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
| playground:fire [2015/10/16 13:05] – jacobs | playground:fire [2026/06/25 16:12] (current) – external edit 127.0.0.1 | ||
|---|---|---|---|
| Line 1: | Line 1: | ||
| - | - Accelerator Personnel do not have any control over the main Fire Alarm Systems, we only have the ability to view information. | + | **Actions if the building |
| - | - If the fire alarm activates: | + | |
| - The designated Accelerator Operator shall: | - The designated Accelerator Operator shall: | ||
| - | * Check the annunciator panel for the location of the alarm (more on the panel below) | + | * Check the annunciator panel for the location of the alarm (instructions |
| * Put in all faraday cups and shut down the accelerator | * Put in all faraday cups and shut down the accelerator | ||
| + | * Contact accelerator staff ASAP | ||
| * Wait for emergency personnel in the lobby and escort them to the location | * Wait for emergency personnel in the lobby and escort them to the location | ||
| - All other personnel are to evacuate the building as directed by the alarm system message | - All other personnel are to evacuate the building as directed by the alarm system message | ||
| - | | + | |
| - | | + | **Actions if the annunciator panel reports Supervisory: |
| - | | + | |
| - | | + | The designated Accelerator Operator shall: |
| + | | ||
| + | - Check the annunciator for the nature of the trouble (instructions on the panel below) | ||
| + | - If the message is "DOCK or VAULT ECO SENSOR ALARM" this is a low oxygen event | ||
| + | - The VESDA computer should be playing a low oxygen message, check to see if the computer is reporting low oxygen. | ||
| + | - Check to see if the SF6 alarm and Tank Volume data support an SF6 leak | ||
| + | - Contact accelerator staff immediately | ||
| + | - Be prepared to go to the nearest fire alarm pull station to evacuate the building | ||
| + | - If the message is " | ||
| + | - Contact accelerator staff immediately | ||
| + | - Activate the Tritium Exhaust Fans | ||
| + | - Be aware that the building fire alarm may activate soon | ||
| + | |||
| + | **Actions if the annunciator panel reports Trouble: | ||
| + | |||
| + | The designated Accelerator Operator shall: | ||
| + | - Immediately stop radiation production | ||
| + | - Check the annunciator for the nature of the trouble (instructions on the panel below) | ||
| + | - If the message is " | ||
| + | - Contact accelerator staff immediately | ||
| + | - Be aware that the Supervisory Trouble and then the building fire alarm may activate soon | ||
| + | |||
| + | __........................................................................................__ | ||
| + | |||
| + | **General Information: | ||
| + | * Accelerator Personnel do not have any control over the main Fire Alarm Systems, we only have the ability to view information. | ||
| + | * If the fire alarm is in a condition other than normal, no radiation will be produced until the trouble is fixed, or until the requirements in the Interlock Rules Policy have been satisfied. | ||
| + | | ||
| + | | ||
| + | | ||
| **The Annunciator Panel** (located in the control room, photo below) | **The Annunciator Panel** (located in the control room, photo below) | ||
playground/fire.1445015124.txt.gz · Last modified: (external edit)