playground:fire
Differences
This shows you the differences between two versions of the page.
| Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
| playground:fire [2012/06/13 09:15] – jacobs | playground:fire [2026/06/25 16:12] (current) – external edit 127.0.0.1 | ||
|---|---|---|---|
| Line 1: | Line 1: | ||
| - | - Accelerator Personnel do not have any control over the Fire Alarm Systems, we only have the ability to view information. | + | **Actions if the building |
| - | - If the fire alarm activates: | + | |
| - The designated Accelerator Operator shall: | - The designated Accelerator Operator shall: | ||
| - | * Check the annunciator panel for the location of the alarm (more on the panel below) | + | * Check the annunciator panel for the location of the alarm (instructions |
| * Put in all faraday cups and shut down the accelerator | * Put in all faraday cups and shut down the accelerator | ||
| + | * Contact accelerator staff ASAP | ||
| * Wait for emergency personnel in the lobby and escort them to the location | * Wait for emergency personnel in the lobby and escort them to the location | ||
| - All other personnel are to evacuate the building as directed by the alarm system message | - All other personnel are to evacuate the building as directed by the alarm system message | ||
| - | - If the fire alarm is in a trouble condition no radiation will be produced until the trouble is fixed, or until the requirements in the Interlock Rules Policy have been satisfied. | ||
| - | - Accelerator Personnel may use a fire extinguisher if the individual feels they can do so safely but there is no requirement to do so. | ||
| - | - Never open a door to an alarm area if smoke is visible outside the door or if the door is warm. | ||
| - | **The Annunciator Panel** (located in the control room, photo below) | + | **Actions if the annunciator panel reports Supervisory: |
| - | There are 4 possible conditions | + | The designated Accelerator Operator shall: |
| - | * System Normal: The LCD displays "sytem normal" | + | - Immediately stop radiation production |
| - | * Fire Alarm: | + | - Check the annunciator |
| + | - If the message | ||
| + | - The VESDA computer should | ||
| + | - Check to see if the SF6 alarm and Tank Volume data support an SF6 leak | ||
| + | - Contact accelerator staff immediately | ||
| + | - Be prepared to go to the nearest fire alarm pull station to evacuate the building | ||
| + | - If the message is " | ||
| + | - Contact accelerator staff immediately | ||
| + | - Activate the Tritium Exhaust Fans | ||
| + | - Be aware that the building fire alarm may activate soon | ||
| + | **Actions if the annunciator panel reports Trouble:** | ||
| + | The designated Accelerator Operator shall: | ||
| + | - Immediately stop radiation production | ||
| + | - Check the annunciator for the nature of the trouble (instructions on the panel below) | ||
| + | - If the message is " | ||
| + | - Contact accelerator staff immediately | ||
| + | - Be aware that the Supervisory Trouble and then the building fire alarm may activate soon | ||
| + | __........................................................................................__ | ||
| + | **General Information: | ||
| + | * Accelerator Personnel do not have any control over the main Fire Alarm Systems, we only have the ability to view information. | ||
| + | * If the fire alarm is in a condition other than normal, no radiation will be produced until the trouble is fixed, or until the requirements in the Interlock Rules Policy have been satisfied. | ||
| + | * Accelerator Personnel may use a fire extinguisher if the individual feels they can do so safely but there is no requirement to do so. | ||
| + | * Never open a door to an alarm area if smoke is visible outside the door or if the door is warm. | ||
| + | * OUPD dispatchers should get automatically notified of any trouble or fire alarm on the system. | ||
| + | **The Annunciator Panel** (located in the control room, photo below) | ||
| + | The control room annunciator is the only point where accelerator personnel have access to system information. | ||
| + | There are 4 possible conditions for the fire alarm system: | ||
| + | * **System Normal**: The LCD displays "sytem normal" | ||
| + | * **Fire Alarm**: | ||
| + | * **System Supervisory**: | ||
| + | * **System Trouble**: | ||
| + | The Priority 2 alarm is not used in our system and we should not ever see such alarms. | ||
| + | The gray buttons and LEDs on the left side of the annunciator do nothing for us. The LEDs may illuminated during maintenance to indicate that certain functions are disabled for repairs. | ||
| - | {{playground: | + | |
| + | {{playground: | ||